Constant rise in price of the petroleum products on the internal and external markets forces the enterprises to search for paths of cost-saving of production. Important component of the product cost for enterprises is the electric power.
The cost-effective and easy-to-maintain, 30KW - 1MW power output, Automation Level I, II, III gas-piston power stations offer the optimum solution to meet the on-site operational demand for low-cost electric power and heat supply.
With the use of the Russian-built gas-piston power stations, the electric power generation, transmission and consumption processes take place directly on your operational premises. This advanced approach affords a considerable reduction of the electric power cost, thus ensuring a lower overall product cost and boosting the profitability level of your production operations.
The gas-piston power stations run on such fuel types as the pipeline gas, pit methane, associated petroleum gas (with 20% minimum methane content, or up to 0.2% maximum mass content of hydrogen sulphide).
|
Specifications |
AGP-
30S-
T400-1R |
AGP-
60S-
T400-1R |
AGP-
100S-
T400-1R |
AGP-
150S-
T400-1R |
AGP-
200S-
T400-1R |
AGP-
250S-
T400-1R |
AGP-
315S-
T400-1R |
AGP-
350S-
T400-1R |
Rated power (continuous),
kW / kWA |
30/37,5 |
60/75 |
100/125 |
150/187,5 |
200/250 |
250/312,5 |
315/394 |
350/476 |
Maximum one-hour rating,
kW / kWA |
33/41,25 |
66/82,5 |
110/137,5 |
166/206,25 |
220/275 |
275/343,75 |
346/471 |
385/524 |
| Ampere rating, A |
54 |
108 |
180 |
270 |
360 |
450 |
570 |
630 |
| Cooling system |
17 |
36 |
36 |
36 |
60 |
70 |
85 |
85 |
| Lubricating system |
12 |
34 |
34 |
34 |
34 |
33 |
50 |
50 |
Specific fuel
consumption at rated
power, m3/hour |
15 |
24 |
35 |
35 |
70 |
87,5 |
112,2 |
125,2 |
Specific oil consumption,
% from a fuel consumption |
0,5 |
0,5 |
0,5 |
0,5 |
0,5 |
0,5 |
0,5 |
0,5 |
Overall dimensions,
mm (length, width, height) |
2360
960
1310 |
2271*
1040*
1145 |
2450*
1040
1145 |
2760
1342
1625 |
2865
1233
1175 |
2910
1172
1720 |
3450(3025)
1300(1600)
1700 |
3450(3025)
1300(1600)
1700 |
Mass of dry electrical
unit, kg |
1300 |
1800 |
2050* |
2600 |
2700 |
3150 |
4000 |
4000 |
Guaranteed operating
time, m. hours |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
3000 |
| Overhaul life, m. hours |
10000 |
10000 |
16000 |
20000 |
16000 |
20000 |
20000 |
20000 |
|